True online double-conversion UPS with pure sine wave output, zero transfer time to battery and complete UPS replacement capability with no downtime, SU6000RT4UHV provides the highest level of protection available for mission-critical equipment from power outages, voltage fluctuations and transient surges. It converts incoming AC power to DC and reconverts it back to filtered AC output with a pure sine wave, isolating connected components from all power problems in high-voltage environments. SU6000RT4UHV has a 6kVA/5400W capacity and 4 AC outlets (2 L6-20R and 2 L6-30R). With its detachable PDU, the SU6000RT4UHV is easily hot-swappable by a user of any skill set - no need for lengthy and expensive service calls and no downtime if a repair or battery replacement is needed. In bypass mode, the PDU passes power to equipment without the use of the power and battery modules, allowing them to be removed while keeping your application in operation. UPS battery backup keeps connected equipment operational through short power failures and provides time to save data and perform an orderly system shutdown in case of a prolonged blackout. The SU6000RT4UHV‘s runtime can be expanded with optional external battery packs. SU6000RT4UHV features a highly efficient (96%) economy mode setting that can significantly reduce a facility's energy costs by minimizing heat output, reducing cooling requirements and consuming less electricity. LCD display with LED indicators enables IT personnel to monitor operating modes and conditions. LCD/LED panel rotates for viewing in horizontal rack or vertical tower installations and includes an audible alarm that signals various conditions. SU6000RT4UHV features a USB port and a DB9 port that, when used with Tripp Lite's included PowerAlert software, provide comprehensive network power monitoring and control. Optional SNMPWEBCARD accessory can enable the UPS to operate as an IP managed device. Unit requires only 4U of rack space in a standard rack enclosure and can be installed in a 2-post rack using the 2POSTRMKITHD accessory, or in a tower configuration with the 2-9USTAND accessory.
Fault tolerant electronic bypass
Detachable back panel PDU
L6-30P input plug, two L6-30R and two L6-20R outlets
Included rail kit supports 4U 19-inch rack-mount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (1 required for SU6000RT4UHV)
Optional 2-9USTAND supports upright tower placement (1 required for SU6000RT4UHV)
Maximum installed rack depth of only 20.7 inches/52.6cm
Maintains full-time sine wave output within 2% of selected 200/208/220/230/240V nominal in double conversion mode
Corrects brownouts to 156V at full load (100V at 50% load or less)
Corrects overvoltages to 290V at full load (300V at 90% load or less)
Supports 50/60Hz operation for worldwide frequency compatibility
Double-conversion operation
High efficiency economy mode operation
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions
UPS card slot supports one card-based network interface option or dry-contact monitoring accessory
Optional SNMPWEBCARD
Optional RELAYIOCARD
Optional RELAYIOMINI interface module
HID-compliant USB interface
Includes free PowerAlert monitoring software packages
Front panel LEDs and LCD readout
LED/LCD display panel
Supports emergency power off (EPO) via built-in interface
Battery independent restart
BP192V12-3U external battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60 to 50 or 60 to 50Hz (no de-rating)
Rated input current (at maximum load):
26.6/27.7/29/30.6/31.9 A
Nominal Input Voltage:
200/208/220/230/240 VAC
Input Connection Type:
L6-30P
Battery Full Load Runtime:
2 minutes (5400W)
Battery Half Load Runtime:
8.5 minutes (2700W)
DC Battery System Voltage:
192 VDC
AC Mode Output AC Waveform:
Pure sine wave
Battery Mode Output AC Waveform:
Pure sine wave
Battery recharge rate (included batteries):
6 hours (10 to 90%)
Primary Form Factor:
Rack-mount
Cooling Method:
Fan
UPS housing material:
Steel
Shipping Dimensions:
12.7 x 23.6 x 29.1 inches
Package Includes:
SU6000RT3UPM 3U UPS power module, BP240V10RT3U 3U external battery pack, PowerAlert UPS management software and complete cabling, mounting hardware to support each 3U module in 4 post rack enclosures, 2-9USTAND tower stand set, warranty information and instruction manual
RoHS Compliant:
Yes
Operating Temperature (Maximum):
104 F
Operating Temperature (Minimum):
32 F
Cord Length (in/mm):
118.11 in
Estimated Runtime:
2 minutes
Estimated Runtime:
0.03 hours
Number of Outlets:
4
Rack Units (Height):
4
Rackmountable:
Yes
UL Rated:
Yes
Depth:
20.70 in
Height:
6.85 in
Width:
17.50 in
Product Weight:
108.03 lbs
Shipping Weight:
158.07 lbs
Warranty (Length/Type):
2-year Limited
BP192V12-3U
- External 192V 3U Rack/Tower Battery Pack for select Tripp Lite UPS Systems (BP192V12-3U)