6kVA/5400W online double-conversion UPS system is offers complete power protection for critical server, network and telecommunications equipment in a single 4U rack/tower compatible housing. Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise. Fault-tolerant auto-bypass prevents unexpected service interruptions during UPS overload or internal fault conditions. Detachable back panel PDU with manual bypass switch supports hot-swappable whole UPS replacement with no interruption to connected equipment. Single all-in-one rack / tower housing installs in only 4 rack spaces (4U) with a maximum installed depth of only 20.7 inches/52.6cm. Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal during brownouts as low 100V and overvoltages as high as 300V. Expandable runtime is supported with optional BP192V12-3U external battery packs. Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement. Double-conversion operation converts raw input from AC to DC, then resynthesizes output power back to perfect sine wave AC with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs. Network-grade AC surge and noise suppression. Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces. Optional SNMP/Web and contact-closure communications card accessories available. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as UPS batteries become depleted. Included software packages include PowerAlert Local, PowerAlert Network Shutdown Agent and PowerAlert Network Management System for complete support for a wide variety of application types. Supports emergency power off (EPO) via built-in interface. Front panel LEDs and LCD readout with scroll controls support front-panel visual monitoring of all major UPS for a variety of control options to
Fault tolerant electronic bypass
Detachable back panel PDU
Hardwire input and 4 C19 output receptacles
Included rail kit supports 4U 19-inch rack-mount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (1 required for SU6000RT4UHVG)
Optional 2-9USTAND supports upright tower placement (1 required for SU6000RT4UHVG)
Maximum installed rack depth of only 20.7 inches/52.6cm
Maintains full-time sine wave output within 2% of selected 200/208/220/230/240V nominal in double conversion mode
Corrects brownouts to 156V at full load (100V at 50% load or less)
Corrects overvoltages to 290V at full load (300V at 90% load or less)
Supports 50/60Hz operation for worldwide frequency compatibility
Double-conversion operation
High efficiency economy mode operation
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions
UPS card slot supports one card-based network interface option or dry-contact monitoring accessory
Optional SNMPWEBCARD
Optional RELAYIOCARD
Optional RELAYIOMINI interface module
HID-compliant USB interface
Includes free PowerAlert monitoring software packages
Front panel LEDs and LCD readout
LED/LCD display panel
Supports emergency power off (EPO) via built-in interface
Battery independent restart
BP192V12-3U external battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60 to 50 or 50 to 60Hz (no de-rating)
Warranty - Yes
Rackmountable - Yes
UL Rated - Yes
Spec Sheet available - Yes
Output volt amp capacity:
6000 VA
Output Watt Capacity:
5400 W
Nominal Output Voltage:
200/208/220/230/240 V
Frequency Compatibility:
50/60 Hz
Built-in UPS output receptacles:
4 C19 outlets
Rated input current (at maximum load):
26.6/27.7/29/30.6/31.9 A
Nominal Input Voltage:
200/208/220/230/240 VAC
Input Connection Type:
Hardwire
Battery Full Load Runtime:
2 minutes (5400W)
Battery Half Load Runtime:
8.5 minutes (2700W)
DC Battery System Voltage:
192 VDC
AC Mode Output AC Waveform:
Pure sine wave
Battery Mode Output AC Waveform:
Pure sine wave
Battery recharge rate (included batteries):
6 hours (10 to 90%)
Primary Form Factor:
Rack-mount
Cooling Method:
Fan
UPS housing material:
Steel
Shipping Dimensions:
12.7 x 23.6 x 29.1 inches
Package Includes:
SU6000RT4UHVPM hot-swappable UPS power module, SUPDMB6KIEC detachable PDU with maintenance bypass switch, PowerAlert software CD, 1 x 6ft USB cable, 1 x 6ft DB9 cable and 4-post rack-mount hardware
RoHS Compliant:
Yes
Operating Temperature (Maximum):
104 F
Operating Temperature (Minimum):
32 F
Estimated Runtime:
2 minutes
Estimated Runtime:
0.03 hours
Number of Outlets:
4
Rack Units (Height):
4
Rackmountable:
Yes
UL Rated:
Yes
Depth:
20.70 in
Height:
6.85 in
Width:
17.50 in
Product Weight:
108.03 lbs
Shipping Weight:
345.02 lbs
Warranty (Length/Type):
2-year Limited
BP192V12-3U
- External 192V 3U Rack/Tower Battery Pack for select Tripp Lite UPS Systems (BP192V12-3U)